FCE 99M-PVS-R

CALIBRATED LEAK EN14624

CALIBRATED LEAK

R134a, R1234ze, R1234yf, R600a, R290

The FCE99M-PVS-R calibrated leak is intended for checking the sensitivity and calibration of construction site and production leak detectors operating by sniffing at atmospheric pressure according to the EN 14624 standard.

In the same range:

For an adjustable leak (rather than a fixed value of 3 or 5 g/year), the FCE 24-PVA-DR adjustable leak features a built-in dual tank (expansion chamber + liquid gas reservoir) for HFC HFO HC refrigerant gases.

Compatible with:

The FCE 99M-PVS-R calibration leak compliant with the EN 14624 standard enables sensitivity testing of refrigerant gas detectors: DXR 240, HRD 92 SC and MTD 920.

  • Standard leak value of 3 g/year or 5 g/yr at gas vapor pressure at 20°C.
  • Designed to be supplied with gas in saturated vapor phase.
  • It has its own gas tank in liquid phase. SCHRADER type filling valve ¼ SAE male.
  • Delivered with a calibration certificate and a pressure-temperature/leakage flow correspondence curve.

Can be delivered for:

  • R134a, R1234ze, R1234yf, R600a, R290.
UseThe FCE 99M-PVS-R leak is a continuous flow leak, it has its own gas reservoir in liquid phase. SCHRADER type filling valve ¼ SAE male.
Leak value

3 g/yr [+/-20%] at the vapor pressure of the gas at 20°C.

5 g/yr [+/-20%] at the vapor pressure of the gas at 20°C.

Other values, contact us.

Gas

R134a, R1234ze, R1234yf,  R600a, R290.

Other gases contact us.

Delivred withLeak delivered with its calibration certificate valid for 1 year and a pressure-temperature/leak flow correspondence curve.