HRD 92 E

REFRIGERANT GAS LEAK DETECTOR HFO, HFC, HC & H2/N2

FORMING GAS, N2/H2 TRACER GAS & NIDRON

The HRD 92 E is a portable gas leak detector for the detection of refrigerant gases (HFC, HFO, HC), the H2/N2 tracer mixture (forming gas). Designed for leak testing by sniffing at atmospheric pressure.

In the same range:

For portable use more focused on field inspection with graphic display and 3 sensitivity positions, the DXR 240 is the direct alternative on the same gases HFC, HFO, HC and H2/N2. For high-sensitivity tightness control on production lines or expert use, the MTD 920 provides automatic calibration on a calibrated leak and displays the estimated leak rate value.

Accessories:

For testing compliant with the EN 14624 standard, use the FCE 99M-PVS-R calibrated leak at 5 g/year. For verification with a specific leak rate on other gases, use the FCH 99M-PVA-R150 adjustable calibrated leak with its built-in tank, delivered with a pressure/flow curve.

  • Industrial detector for the detection of refrigerant gases and H2/N2 tracer gas.
  • Selection of gas type.
  • Graduated graphic ramp allowing an estimation of the leak detected.

2 Detection Modes :

  • AUTO mode.
  • TRACKING mode.

2 Detection blocks type :

  • Detection block for all refrigerant gases HFO, HFC, HC (1234ze, R134a, R404, R407, R410, R32… R290, R600, NH3)
  • Selective detection block for H2/N2 tracer mixture.
Functions

Gas type selector.

3 sensitivity positions.

AUTO detection mode & TRACKING mode with manual zero on the ambient atmosphere.

Contamination-saturation indication.

Interchangeable detection block.

Display

Graphic touch screen.

Graduated graphic ramp with sound signal.

SensorElectrochemical.
Detected gases

Block for all refrigerant gases: HFC (R134a, R404, R407, R410, R32…), HFO (R1234ze, R1234yf…), R600, R290, H2/N2.

Specific tracer gas block: H2/N2, NIDRON.

Sensitivity

HFC, HFO : 1 g/yr.

R600 & R290 : 0.5 g/yr.

H2/N2 tracer gas mixture, NIDRON: 1.10-5 cc/s [equivalent approx. 1 g/yr refrigerant gases].

Autonomy4h
Power supplyBuilt-in rechargeable batteries. Charging time around 12 hours.
Delivered with

Detector delivered complete in transport case with mains charger and instructions for use.

Protective rubber sock included.

Option

Lighting block.

Adjustable pipe 30cm.

IN THE SAME CATEGORY