FCE 99M-PVS-R
CALIBRATED LEAK EN14624
CALIBRATED LEAK
R134a, R1234ze, R1234yf, R600a, R290
The FCE99M-PVS-R calibrated leak is intended for checking the sensitivity and calibration of construction site and production leak detectors operating by sniffing at atmospheric pressure according to the EN 14624 standard.
- Standard leak value of 3 g/year or 5 g/yr at gas vapor pressure at 20°C.
- Designed to be supplied with gas in saturated vapor phase.
- It has its own gas tank in liquid phase. SCHRADER type filling valve ¼ SAE male.
- Delivered with a calibration certificate and a pressure-temperature/leakage flow correspondence curve.
Can be delivered for:
- R134a, R1234ze, R1234yf, R600a, R290.
Use | The FCE 99M-PVS-R leak is a continuous flow leak, it has its own gas reservoir in liquid phase. SCHRADER type filling valve ¼ SAE male. |
Leak value | 3 g/yr [+/-20%] at the vapor pressure of the gas at 20°C. 5 g/yr [+/-20%] at the vapor pressure of the gas at 20°C. Other values, contact us. |
Gas | R134a, R1234ze, R1234yf, R600a, R290. Other gases contact us. |
Delivred with | Leak delivered with its calibration certificate valid for 1 year and a pressure-temperature/leak flow correspondence curve. |